            BURKERT控制器1150系列技術(shù)參數(shù): 

            Controller structure

            P, I, PD, PI, PID

            PID

            Control loop feedback

            Proportional band

            0

            to 9999 digits

            0 digits

            Size of the proportional band

             

             

             

             

            0 means that the controller structure is out of action!

            Derivative time

            0

            to 9999 sec

            80 sec

            Determines the differential component of the controller output signal

            Reset time

            0

            to 9999 sec

            350 sec

            Determines the integral component of the controller output signal

            Cycle time

            0

            to 9999 sec

            20 sec

            When using a switched output, the cycle time should be chosen so

             

             

             

             

            that the energy fl ow to the process is quasi continuous, i.e. as con-

             

             

             

             

            tinuous as is practicable without overloading the switching elements

            Contact spacing

            0

            to 999 sec

            0 digits

            The spacing between the two controller contacts for double-

             

             

             

             

            setpoint or modulating controllers, or proportional controllers

             

             

             

             

            with an integrated actuator driver

            Switching differential

            0

            to 999 digits

            1 digits

            Hysteresis for switching controllers with proportional band = 0

            Actuator time

            5

            to 3000 sec

            60 sec

            The actually utilized operating time of the regulator valve with

             

             

             

             

            modulating controllers or proportional controllers with an integrated

             

             

             

             

            actuator driver

            Working point

            -100

            to +100%

            0%

            The output level for P and PD controllers (if x = w then y = Y0)

            Output level limiting

            0

            to 100%

            100%

            The maximum limit for the output level

             

            -100

            to +100%

            -100%

            The minimum limit for the output level

            Minimum relay ON time

            0

            to 60 sec

            0 sec

            Limits the frequency of switching for switched outputs